As per current NATSPEC.
As per current NATSPEC.
As per current NATSPEC.
As per current NATSPEC except as follows:
GUIDE NOTE: Insert project specific locations. Refer to the Educational Facilities Standards and Guidelines.
Location
>
Construction
General: Steel tubular section with welded plate capping, all hot dip galvanised after fabrication, and set in a concrete footing.
Hot dip galvanising: To AS 4680
Installation: Set 300 mm deep in concrete footing
Pipe size: 125 mm nominal OD x 5.4 mm wall thickness
Height: 900 mm from pavement level
Capping: 6 mm thick mild steel plate
Concrete footing: 300 x 300 x 450 mm deep
Drawing reference
Location
>
General
A proprietary lockable demountable metal tubular section bollard with a dome head capping.
Tubular section: To AS 1163
Head: Cast aluminium
Height: 900 mm above ground level
Demounting plate assembly
A proprietary compatible surface demounting plate assembly complete with pin guide and heavy duty pin with provision for padlock, all hot dip galvanised after fabrication (including pin).
Hot dip galvanising: To AS 4680
Height: 60 mm maximum
Pin: 12.5 mm hole in pin to receive padlock
Fixing holes: 2 (minimum), concealed
Fixing: Surface fixed with fasteners through mounting holes in demounting plate
Bollard sleeve: Fill with concrete, finish in dome shape
Padlock
Refer to SG / DOOR HARDWARE
Construction
Fabricate from 1.25mm sheet steel, with penetration for piping. Weld door hinges to frame.
Mounting: To AS 1221
Finish: Primer and 2 coats enamel.
Colour: Enamel - Red
Sign: "FIRE HOSE" in white
Type:
>
Size: 1210mm x 840mm opening
Doors: Pressed 1.25mm steel sheet, fit with chrome plated handle
Fixing:
>
General
Select suitable item or design and construct the fire hydrant security cover to suit specific fire hydrant booster valve.
The fire hydrant security cover must be in compliance with all the necessary statutory authorities’ requirements.
Proprietary item:
Padlock
Refer to SG / DOOR HARDWARE
Location
Main Switchroom
Construction
General: Fabricate mild steel frame, support channels, covers, lifting handles and hooks, weld and hot dip galvanize after fabrication.
Frame: Weld from 50 x 50 x 6mm steel angle with hook rods and cast securely into perimeter of concrete pit.
Support channels: Weld 75 x 50 x 10mm channels as intermediate supports.
Perimeter finish strip: Weld a continuous 20mm wide x 10mm thick mild steel flat to the outside perimeter of frame level with floor finish.
Covers: Provide chequerplate aluminium covers of suitable size and weight to enable one person to remove covers without difficulty. The covers are required to take the load of foot traffic only. Each cover is to have two "D" lifting handles. Bolt fix frame with allowances for covers to be removed for access to pit covers
Handles: Provide 2 x 200mm "D" lifting handles bent out of 10mm diameter rod with 50mm studs at each end.
Hooks: Fabricate from 6mm diameter rod 100mm long, bend last 18mm through 90o.
Location
Project Store - Type 1
Construction
Type: Galvanised tubular steel (pipe rail) frame with chain wire mesh barrier and gate.
Standards: Generally to AS1725
Pipe frame (chain wire mesh wall frame)
Sliding single gate – Pipe frame
Reconditioning damaged galvanised surfaces: If possible complete fabrication before galvanising; otherwise apply a zinc-rich primer to affected joint surfaces.
Location
>
Refer to the Electrical drawings.
Construction
Type: Galvanised steel tubular bar securely fixed to ceiling structure to ensure minimum deflection when fully loaded with stage spotlights.
Galvanised tubular lighting bar
Provision for wiring
GUIDE NOTE: Insert project specific locations. Refer to the Educational Facilities Standards and Guidelines.
Location
>
Construction
Material: Stainless steel hook
Fixing: Fix securely to ceiling structure or concrete soffit
Performance: Capable of supporting the following weight:
Location
Access Toilets, Access Showers, Ambulant Toilets, Moderate Unit Toilets and the like. Refer to the drawings.
Type
Tubular metal rail, bent to shape as required, with pre drilled welded end flange plates.
Lengths and dimensions: Refer to the drawings.
Number:
>
Standards
All fittings and installation must comply with AS1428.1 and 2.
Safety grip rails
Where rails are used in shower or bath areas provide safety grip rails with knurling on straight grip surfaces.
Rails
Material: Satin finish stainless steel to AS 1449 - Type 304.
Fabrication
Fully welded joints, grind and polish smooth.
Fixing
Securely fix to wall through pre-drilled holes in flange plates. Fixing screws/bolts are to be stainless steel and are to be supplied by the manufacturer including all accessories; all fixed in accordance with the manufacturers recommendations.
Fixing
Securely fix to wall through pre-drilled holes in flange plates. Fixing screws/bolts are to be stainless steel and are to be supplied by the manufacturer including all accessories; all fixed in accordance with the manufacturers recommendations.
Location
>
Standards
All fittings and installation must comply with AS1428.1 and 2.
Type
Securely fix to wall. Fixing screws/bolts and accessories are to be supplied by the manufacturer and fixed in accordance with the manufacturers recommendations.
Location
Access Toilets, Access Showers, Moderate Unit Toilets and the like. Refer to the drawings.
Standards
All fittings and installation must comply with AS1428.1 and 2.
Construction
Type: Adjustable, vandal resistant backrest
Frame and mounts: Satin finish stainless steel – Type 304
Fixing plates: Mounted at approximately 560mm centres
Backrest: Curved stainless steel
Fixings: Concealed fixings in accordance with the manufacturer’s recommendations
Location
>
Fabrication
Form brackets from mild steel bar comprising of welded members with pre drilled holes for fastening to wall all as shown on drawing, hot dip galvanise after fabrication.
Hot dip galvanising: To AS 4680
Bracket
Material: 40 x 6mm thick MS bar.
Spacing: 1200mm maximum centres
Fixing
Attach securely to building structure with fixings through pre-drilled holes in vertical member with bolts into expanding masonry anchors (metal –10mm diam. minimum), coach screws or bolts into timber and bolts into metal, all fasteners to be of metal compatible with the bracket and of equivalent corrosion resistance.
Location
>
Description
Proprietary stainless guard to suit drinking trough. The guard must have a sloping face (approx. 45o) and be capable of being locked (padlocked) in the open and closed position.
Padlocks:
Length: The maximum length 2400mm. If longer lengths required provide multiple trough guards of equal length. (Eg. 3000 mm length = 2 x 1500 mm long trough guards).
Fittings: All lugs and wall fittings must be compatible with the guard.
Stainless Steel:
Drawing: Refer to drawing
>
Fixing: Fix securely to wall with non-corrosive fasteners and expanding masonry anchors (metal) for masonry walls.
Location
>
Bench top support
Legs (front only): 31.8 x 31.8 x 1.2mm stainless SHS.
Wall support: Provide an angle for the full length securely fixed to wall to support bench top.
Refer to:
SG / TIMBER FIXTURES
SG / JOINERY
SG / SANITARY FIXTURES
SG / TAPWARE
Location
>
Fabrication
Use 32mm nominal diameter galvanised steel tubes cap and bend one end.
Installation
Build open end of Tool Peg into brickwork projecting 225mm.
Location
>
Fabrication
Form brackets from mild steel angle comprising of welded pre-drilled vertical and horizontal members with protruding ends splayed at 45 degrees. Hot dip galvanise after fabrication.
Bracket: 30 x 30 x 5mm M.S. angle
Size: 200 x 200mm
Spacing: 500mm maximum centres
Fixing
Fix securely to wall and underside of shelf through pre-drilled holes with galvanised fasteners and anchors.
Location
>
Fabrication
Mild steel bent tubular frame with 75 x 6 mm plate fixed to front face and welded pre-drilled fixing flanges. Hot dip galvanise after fabrication.
Frame
Size: 900 mm high x 325 mm from wall
Diameter: 40 mm N.B
Protective finish: Hot dipped galvanised
Flanges: 100 x 100 x 10 mm M.S. plate
Centres
600 mm
Fixing
Bolt each flange securely into masonry wall and concrete floor with three 10 mm diameter masonry anchors. Plate fixed to front face of frame with M8 x 65 mm galv. bolts.
Location
>
Fabrication
Two M.S. pipes bent and welded to M.S. plate with capping on open end of pipes hose supports. Pre-drill fixing holes weld all together and hot dip galvanise after fabrication.
Wall Plate
6mm thick M.S. 250mm x 300mm drilled to receive four 10mm fixing bolts.
Hose Supports
40mm NB M.S. pipe bent upwards at a radius of 100mm.Provide capping on open end of pipes.
Number
Two
Length
300mm measured from the inside edge of the pipe upturn to outside edge of plate. i.e. 300mm clear space for hose storage.
Spacings
150mm centres fixed 50mm from edge of plate to centre of pipe and 150mm from top of plate to top of hose support pipe bracket.
Protective finish
Heavy galvanizing.
Installation
Fix securely to wall.
Drawing
Refer to drawing >
GUIDE NOTE: Insert project specific locations. Refer to the Educational Facilities Standards and Guidelines.
Location
>
Fabrication
Form brackets from mild steel angles comprising of vertical and horizontal members. Horizontal members equally spaced at a max. of 200mm with angle cleats and front plates. Front plates having a 30mm high lip. Pre-drill fixing holes, Weld all together and hot dip galvanise after fabrication.
Brackets
Number required: 5
Vertical Member
50 x 50 x 6mm
Height: 2050mm
Horizontal Members
50 x 50 x 6mm
Length: 290mm
Number required: 10
Front Plates
85 x 75 x 6mm M.S. to each horizontal arm
Cleats
30 x 30 x 6 x 40mm long at 80mm maximum centres commencing from free end of horizontal arm
Installation
Fix securely through vertical member into wall with compatible, non-corrosive metal anchors at 200mm centres.
Location
>
Fabrication
Form brackets from mild steel angles comprising a vertical fixing member and horizontal carrying members. Horizontal members equally spaced at 300mm maximum centres with front plates having a 30mm high lip. Pre-drill fixing holes and hot dip galvanize after fabrication.
Brackets
Number required: As shown on drawings
Vertical Member
50 x 50 x 6mm
Height: 2150mm
Horizontal Members
50 x 50 x 6mm
Length: 500mm
Number required: 7
Front Plates
85mm x 75mm x 6mm M.S.
Installation
Fix securely through vertical members into wall at 300mm centres.
Location
>
Fabrication
Form mild steel angle and rod weld, pre-drill and galvanise prior to mounting with masonry anchors.
Rack
Height above floor: 1800mm
Length: 3500mm
Wall angle: 50 x 50 x 6mm
Rods: 18mm diameter x 225mm long bent up to 25mm radius
Installation
With bent ends facing up weld from each end of angle 7 rods at 150mm maximum centres and 3 rods equally spaced in between. Fix horizontally with seven 10 mm diameter equally spaced masonry anchors.
Location
>
Fabrication
Form brackets from mild steel angles comprising of a vertical member and three horizontal members spaced at 450mm with front plates having a 30mm high lip. Pre-drill fixing holes, weld all together and hot dip galvanise after fabrication.
Racks
Wall angle: 50 x 50 x 6mm M.S. angle
Pipe support: 50 x 50 x 6mm M.S. angle. Top of bottom support to be 550mm from finished floor level
Length
300mm
Front Plates
85 x 75 x 6mm M.S. angle. with 10mm radius rounding to all edges
Installation
Mount three rack assemblies at 1500mm max. centres fixing securely with four equally spaced 10mm diam. masonry anchors.
Location
>
Fabrication
Form shelving frame from M.S. angles comprising of a vertical member and a horizontal member with M.S. bearing plates welded on each member to enable solid bearing and fixing to wall and floor. Prepare horizontal angle to receive either timber batten finished top or floor grating finished top all as detailed. Pre-drill fixing holes, weld all together and hot dip galvanise after fabrication.
Vertical Member
50 x 50 x 6mm M.S. angle
Height
900mm
Horizontal Member
50 x 50 x 6mm M.S. angle
Length
600mm (From wall to outside edge of frame)
Spacings
Shelving frame 600mm centres
Floor Bearing Plate
80 x 50 x 8mm M.S. plate
Wall Bearing Plate
100 x 50 x 6mm M.S. plate
Timber Batten Finished Top
Refer to SG / JOINERY
Floor Grating Finished Top
Provide grating as detailed and spot weld to frame. (Ensure all spot welding locations are treated with approved anti-corrosive treatment immediately after welding)
Installation
Rest bearing plate of vertical member on finished floor and fix securely with M12 x 75mm masonry anchors into concrete floor. Rest bearing plate of horizontal member on finished wall and fix securely to wall.
Location
Severe Unit - Practical Activities,
Physically Disabled Unit - Practical Activities
Fabrication
Form frame from mild steel angles comprising of vertical members and a horizontal frame for supporting bench top and trough as shown on drawing. Pre-drill members, weld together and hot dip galvanise after fabrication.
Vertical Members
50 x 50 x 5mm
Horizontal Frame
50 x 50 x 5mm
Height
750mm (Top of bench to finished floor level)
Installation
Fix securely through vertical members to wall at 150mm centres.
Location
>
Fabrication
Form shelving frame from mild steel RHS comprising of vertical and horizontal members. Provide pre-drilled M.S. bearing plates welded on each horizontal member and adjustable foot inserts to each vertical member, all as shown on drawings. Pre-drill fixing holes, weld all together and hot dip galvanise after fabrication.
Hot dip galvanising: To AS 4680
Provide Exterior use plywood Bond Type “A” support platform for trough as shown on drawings.
Vertical Member: 35 x 35 x 2.5 mm M.S. RHS.
Height: 800 mm (Finished floor level to top of platform). Allow 1:100 fall in platform towards outlet.
Horizontal Member: 35 x 35 x 2.5 mm M.S. RHS.
Spacings: Shelving frame 600 mm max. centres.
Feet: Adjustable "knock-in" type stainless steel foot inserts (for adjusting frame to provide fall in trough).
Wall Bearing Plate: 80 x 50 x 6 mm M.S. plate
Installation
Securely fix horizontal members through bearing plates to finished wall.
Fix trough support platform to frame with galv. screws through pre-drilled holes in horizontal steel members.
Stainless steel angled fixing lugs on each end of trough are to be screw fixed to RHS frame through plywood platform with stainless steel screws suitable for metal fastening.
Plant Soaking Trough
Refer to SG / SANITARY FIXTURES
Location
Physically Disabled Unit - Practical Activities Size 2
Fabrication
Form brackets from mild steel angle comprising of welded pre-drilled vertical and horizontal members with protuding angle ends splayed at 45 degrees. Hot dip galvanise after fabrication
Bracket: 50 x 50 x 5mm MS angle.
Size: 540 x 540mm
Spacings: 600mm maximum centres.
Fixings
Fix securely to wall and underside of bench top through pre-drilled fixing holes with galvanised fasteners and anchors.
Location
>
Bench top support frame – PA trough/top M79 and SK40, Bench top M81, Craft Sink/top M75 and SK50
Bench top support frame members (nominal): 38 x 25 x 1.6mm RHS
Bench top frame legs (nominal): 50 x 50 x 1.6mm SHS at 810mm maximum centres (nominal).
Floor fixing lug
Fixing
Specification reference: Drawing
>
Location
>
Fabrication
Four mild steel bar brackets with three horizontal legs each, projecting 250mm with end plate having a 20mm high lip upstand. Mitre cut vertical flanges, pre-drill fixing holes, weld all together and hot dip galvanize after fabrication.
Bar Brackets
50 x 50 x 6mm angle.
Legs
50 x 50 x 6mm angle.
End Plates
85 x 70 x 6mm M.S. plate with 15mm radius edges.
Fixing
Fix each bracket securely to the wall with galvanised 12 mm masonry anchors.
Location
>
Fabrication
Bent out of galvanised mild steel flat and pre-drilled prior to fixing.
Height
1400mm
Maximum centres
1750mm
Bar bracket
ent 150mm fixing leg, 100mm horizontal and 75mm upstand.
Fixing
2 x 8mm diameter galvanised bolts into masonry anchors
GUIDE NOTE: Include list of locations where cover panel to stoves are required. Refer to Educational Facilities Standards and Guidelines and Supplements.
Location
>
Description
Where ovens are located back to back provide a metal capping strip with turned down flanges to the top of the stove upstands and down the sides to 90mm above floor.
Material
Stainless Steel
Width
203mm
Thickness
1.2mm
Fabrication
Turn down flanges, 6 mm on all edges, neatly form and solder joints, buff edges to remove sharp projections.
Location
>
Description
A mild steel non-lockable galvanised Laboratory Master Control Box built into brickwork where shown on the Drawings.
Size
600 x 710 x 160 mm
Steel Thickness
1.6 mm
Finish
Baked Enamel
Location
Change Rooms
Fabrication
Form brackets from mild steel angle comprising of vertical and horizontal members with fixing plates on ends of both members as shown on drawings. Pre-drill horizontal member and fixing plates, weld all together and hot dip galvanise after fabrication.
Size:
>
Spacing: 600mm maximum centres.
Fixing: Fix securely to wall and floor through pre-drilled cleats.
Location/s
>
Description
A complete proprietary system including hot dipped galvanised or heavy-duty aluminium seat supports, fixings and anodised aluminium seating complete with end capping as shown on drawings.
Aluminium Seating
Extruded aluminium alloy seat complete with a minimum of two longitudinal flanged ribs as part of the extrusion. The longitudinal ribs must be continuos for the total length of the seat and provide secure fastening to the seat support.
Assembly
Attach seat support to the seat’s longitudinal flanged ribs with special compatible fasteners capable of providing a secure joint between seat and support.
The fastening system must be either a proprietary securing system that requires a mechanical device or a special security key to remove the seat. The seat must be capable of being removed by an authorised person without destroying the seat support.
If a security key is used to fix seat to seat support, hand two security keys to the Principal’s Authorised Person / Principal’s Representative on completion.
End Capping
Cast aluminium
Minimum of 5 pop rivets for each end cap (3 pop rivets at top and 2 at bottom). The manufacturer’s name to be embossed on all end caps
Finish (seats)
Seats: Clear etched and anodised
Seat support: Hot dipped galvanised to AS 4680 after fabrication.
Installation
Installation must be carried out by the manufacturer/supplier of the proprietary aluminium seating.
OR
An installer approved by the manufacturer/supplier of the proprietary aluminium bench seating.
Footings
Set seat support bracket posts in concrete footings minimum
200 x 200 x 250mm deep. Increase footing sizes as required for specific site conditions.
Above Ground Fixing, Concrete
Fix securely with a minimum of 2 non-corrosive compatible masonry anchors or stainless steel fixing spikes through pre-drilled holes in 160 x 80 x 10mm (minimum) flat bottom plate. Bottom plate to be fully welded to the support post.
Fixing method must capable of preventing unwarranted removal of bracket.
Drawing reference:
>
GUIDE NOTE: Insert project specific locations. Refer to the Educational Facilities Standards and Guidelines.
Location
>
Description
A complete proprietary system including aluminium seating and table tops with galvanised steel or aluminium frames.
Length (nominal): 2000 mm
Height (nominal)
Hot dipped galvanised tubular steel or aluminium
Diameter (nominal): 37mm (ID)
Wall thickness (nominal): 2mm
Fixing: Provisions for permanent fixing
Seating and table tops (Feb 2012)
Extruded aluminium alloy complete end capping.
Assembly: Attach to frame by using vandal resistant fastening system.
The fastening system must be either a proprietary securing system or fixing system that requires a mechanical device to remove the seat and tops. The seat and tops must be capable of being removed without destroying the frame.
If security bolts requiring a security key are used to fix seat and table tops to support, hand two security keys to the Principal’s Authorised Person / Principal’s Representative on completion of installation.
End capping
Cast aluminium
Minimum of 5 pop rivets for each end cap (3 top and 2 bottom)
Finish (seats and table tops)
Clear etched and anodised.
Installation
Fix securely to concrete with non-corrosive compatible masonry anchors or stainless steel fixing spikes in locations nominated on drawing/s.
Fixing method must capable of preventing unwarranted removal of assembly.
Location
>
Standards
To AS 2890.3
Compound
Bicycle parking facility to AS 2890.3 – Facility Class 2 (Refer Appendix B Typical Bicycle Parking Facilities – B3 Class 2 - B3.2).
Steel frames (posts, rails)
Weld mesh panels:
Door:
*Roofing
> If roofing is required include the following in the specification description:
Preformed continuous corrugated metal sheet roofing system complete with all necessary fasteners, accessories, trims all in accordance with AS 1562.1. AS 2180 & AS 3566.
Installation: To HB 39 Code of Common Practice for Steel Roofing
(Include appropriate category for location. Refer to AS 2728. Either category 3 or 4.)
Finish: To AS 2728 Category >.
Colour: Refer to Colour Schedule
Footings/ Anchorage
Bicycle Rack:
Standard: To AS 2890.3
Security Compact Bicycle Rack
Location
>
Type
Tubular metal rail bent twice with two welded intermediate wall brackets and pre-drilled end flange plates welded to brackets and curved end mounts.
Nominal size: 25mm I.D.
Material: Stainless steel
Size: 2000mm
Height From Finished floor level: 750mm
Fixing
Securely fix to wall through pre-drilled holes in flange plates.
Location
>
Fabrication
Fabricate from mild steel comprising of vertical and horizontal members with fixed foot plates. Weld altogether as shown on drawings.
Vertical Member
50 x 8 mm MS flat with radius edges
Horizontal Member (Tube)
40 mm NB x 4 mm MS tube.
Horizontal Rail Support:
Installation
Fix securely to floor through pre-drilled holes in floor plates and at each end of mirror assembly through pre drilled holes in end support brackets.
Timber Rail
Refer to SG / JOINERY
Location
>
Description: Stainless steel wire rope is to be supported by eye bolts complete with a turn buckle and all necessary accessories for securing and terminating wire rope.
Wire rope: stainless steel, nylon coated
Eye bolts: Stainless steel
Intermediate eye bolts: Stainless steel
Turnbuckle: Stainless steel
Height from floor: 2360 mm
Location
Darkroom
Description
Stainless steel wire rope is to be supported by galvanised angle brackets drilled and complete with all necessary accessories for securing and terminating wire rope.
Wire rope: Stainless steel, nylon coated.
Brackets: Galvanised steel
Height from floor: 1800mm
Location
>
Fabrication
Form support frame for demonstration mirror from M.S. angle comprising of horizontal, vertical and 35 degree raking members spaced at 1000mm centres. Mirror to be held in position on support frame by mirror framing angle bolted top and bottom to each raking member of the support frame as detailed. Cut flanges, pre-drill fixing holes, weld all together and hot dip galvanise after fabrication.
Support Frame: 40 x 40 x 6mm M.S. angle.
Height: 2700mm - (Ceiling line).
Mirror Assembly: Plastic mirror fixed to backing of 12mm HMR particle board. Support mirror securely with MS framing angle.
Finishing
All metal framing hot dip galvanised.
Fixing
Ceiling fixing: Refer to structural engineer’s drawings.
Mirror
Refer to SG / GLAZING
Drawing
GUIDE NOTE: Refer to the EFSG SG DRAWING / SG404/1.
Location
>
Description
Mirror finished PVC coated bright annealed stainless steel 304 grade, 0.9 mm thickness, Mirror to be folded on all sides, corners welded and buffed, backed with 12 mm thick glue fixed plywood and screw fixed directly to tiled finish/brickwork.
Size: 575 mm x 575 mm for Pupil Toilets,
Height, floor to bottom: 850 mm for Primary
1100 mm for Secondary
Fixing schedule
Type |
Location |
Number off: each space |
Stainless Steel |
Pupil Toilets Up to 5 WC's for |
2 (Butted) 4 (In one group butted together or in two groups of butted pairs). |
|
Up to 10 WC's for girls or boys equivalent. |
6 (Butted together in one or two groups). |
Stainless Steel |
Shower/Change Size 1 |
2. |
|
Shower/Change Size 2 |
1 |
Location
>
Type
Tubular metal rail bent twice with end flange plates.
Rail
GUIDE NOTE: Length may have to be varied to suit specific installations.
Size: 750mm long (nominal) x 25mm OD.
Material: Satin finish stainless steel to AS 1449 - Type 304.
Fabrication: Fully weld, grind and polish smooth.
Fixing
Securely fix to wall with stainless steel fasteners in accordance with the manufacturer's recommendations.
Height from finished floor level
Refer to DG / WATER / HEIGHT OF FITTINGS
Location
Enclosures/cupboards containing gas services
Description
Permanently open type metal ventilators/grilles to provide sufficient ventilation for enclosed areas/cupboards where there is a risk of gas build.
Type:
Position
Fixing: Permanently fixed with adhesive and a minimum of 4 screws per ventilator.