GUIDE NOTE: Refer to Design Guide sections DG/ FABRIC, DG/ MATERIALS AND FINISHES, DG/ FLOOR.
As per current NATSPEC except as follows:
Laying diagram
General: Provide a diagram for each area of resilient flooring showing the location of proposed joints and the laying direction.
Refer to SG / PRELIMINARIES
As per current NATSPEC except as follows:
General
2.0 - 2.5mm thick slip resistant industrial sheet flooring, guaranteed to maintain characteristics for the full thickness and to not require scrubbing, to AS/NZS 4586 and HB197
General
Resilient tactile ground surface indicators for orientation of people with vision impairment in accordance with the NCC
Description
Selections
Hardwearing UV stable high shear strength PVC rubber blend tile suitable for exterior and interior use.
OR
UV stable cork and rubber composition tile suitable for exterior and interior use.
GUIDE NOTE: Select a contrasting colour achieve the required luminance contract with adjacent surfaces.
Requirement
Order and confirm delivery instructions with the resilient flooring preferred subcontractor or selected subcontractors not less than 12 weeks prior to the date required and give 2 weeks notice to the subcontractor of the required laying date.
Give a copy of the delivery docket to the Principal’s Authorised Person / Principal’s Representative on delivery of the material to site with the following details:
As per current NATSPEC except as follows:
Time of laying
The resilient flooring must be laid prior to the carpet.
Change of finish
Junction between resilient flooring and carpet: The carpet edge stripping is to cover the edge of the exposed resilient flooring.
Welded joints
Requirement: If the floor finish cannot be heat welded, cold weld by applying the recommended adhesive to both edges. All joints are to be sealed to prevent moisture penetration.
Maintenance manual
In addition to the maintenance manual supply laminated instructions (see below). The instructions must clearly indicate the location of all resilient floor finishes and the required maintenance requirements showing daily, weekly, monthly and annual requirements. Include the names and addresses of the suppliers, manufacturers and range names and colour of each component
Size: A4 (minimum)
Instructions: Brief, precise with corresponding graphics
Finish: Laminated
Location/Distribution:
Installation: Fasten to wall in a clearly displayed position.
As per current NATSPEC.
Performance Criteria
Selections should be based on the following performance criteria: