Technical Data
Acoustics
N/A
|
Ceiling
ACC
ACOUSTIC CEILING TYPENRC >0.85 highly absorptive ceiling. Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTS2 double data points required. Refer to DG / COMMUNICATIONS WIRELESS ACCESS POINTS |
Cooling
|
Doors
DT
DOOR TYPEMinimum 1m wide door Refer to DG / DOORS DOOR GLAZINGHalf Glazed doors from adjacent Main Area. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES1 drainage outlet. Refer to DG / DRAINAGE |
Fire Protection
PFE
PORTABLE FIRE EXTINGUISHER/ BLANKETPortable fire extinguisher/fire blanket - to comply with NCC. FIRE HOSE REELFire Hose Reels as required to comply with NCC. Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHISF - Industrial sheet flooring to Kitchen area. Refer to DG / FLOOR |
|
Heating
H
HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
|
Keying
KY
KEYING GENERALKeyed to Differ (KD). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
DL
DAYLIGHTDaylight is recommended for this space. |
Power
GPO
GENERAL POWER OUTLETS6 double socket outlets. Refer to DG / POWER |
|
Security
D
SECURITY LEVEL DCategory D - Moderately High Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"PRINTING/PREPARATION" Refer to DG / DOOR SIGNS SIGNS GENERALWARNING NOTICE "ENSURE VENTILATION SYSTEM IN OPERATION", in a conspicuous position. Hazardous Materials sign "FLAMMABLE LIQUID" - class 3, on the exterior of door. Refer to DG / SIGNS |
Ventilation
EXH
GENERAL EXHAUSTGeneral Exhausted required. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHER450mm high Splashback to Sink and Bench. Refer to SG / LINING |
Water
HW
TEMPERED WATERRequired to 1 x sink. Refer to DG / WATER COLD WATERRequired to 1 x sink. Refer to DG / WATER |
Windows
Y
WINDOWS - YWindows are required for this space. |